BioCel® I

  • MERV 16 efficiency for excellent protection against airborne lung-damaging and disease-carrying particles
  • Upgrade efficiency of existing box style filters to near-HEPA levels without requiring special frames or latches
  • Rigid, all-metal construction and water-resistant media
  • Open header design prevents dirty air bypass and makes handling safer and easier
  • Engineered to perform in critical applications under the most difficult operating conditions, including:
  • Temperatures up to 350°F
  • High Humidity
  • Turbulent airflows
  • Repeated fan shutdown
I AM INTERESTED

Description

[vc_row][vc_column width=”1/2″][vc_column_text woodmart_inline=”no” text_larger=”no”]Upgraded Protection

Rated at 95% efficiency on 0.3 micrometers, and MERV 16 per ASHRAE Standard 52.2, the BioCel I filter offers well over 99% average efficiency on 0.5μ to 5.0μ particles, the range encompassing the sizes of most bacteria, virus-carrying particles, and other small particles harmful to human health. The BioCel I has the advantage of a much lower pressure drop than a standard-capacity HEPA filter (0.4″ versus 1.0″ w.g. at 250 FPM) or a high-capacity HEPA filter (0.95″ w.g. vs 1.4″ at 500 FPM).

BioCel I filters fill the gap between ASHRAE-grade high-efficiency filters and ultra-high efficiency HEPAs at half the weight and pressure drop. This compact, lightweight filter will withstand operating temperatures up to 350˚F. To maximize filter life, use BioCel I filters with high-quality AAF Flanders prefilters.[/vc_column_text][/vc_column][vc_column width=”1/2″][vc_column_text woodmart_inline=”no” text_larger=”no”]Rugged Construction

BioCel I filters consist of a pleated media pack enclosed in a galvanized steel frame assembly. The media is made of ultra-fine fiberglass formed into a series of pleats. Corrugated aluminum separators maintain uniform spacing between each pleat to allow unrestricted airflow through the filter. Bar braces are installed on both sides of the filter for extra reinforcement of the media pack. A flattened, expanded faceguard installed on both sides of the filter is available as an option.

BioCel I filters have a single-piece galvanized steel header on the air-entering side that is interlocked to the cell sides in a patented fashion, preventing leakage and forming a totally rigid construction.[/vc_column_text][vc_column_text woodmart_inline=”no” text_larger=”no”]Consult product brochure[/vc_column_text][/vc_column][/vc_row]

Additional information

Efficiency

MERV 16

Filter Depth

12"

Media Type

Fiberglass

Frame Material

Plastic

Separator Style

Gluebead

Special Size Available

No

Antimicrobial Available

Yes

Maximum operation temperature

176˚F (80˚C)

Certification

UL900